What is the current flow on primary of 120:24V single-phase transformer (100% efficient) if load is 1.5A?

Answer this question

  • What is the current flow on primary of 120:24V single-phase transformer (100% efficient) if load is 1.5A?


Answers

Answer #1 | 08/02 2014 12:50
The turns ratio is 5, so the primary current is .3 amps. This neglects the magnetizing current, which should be much less than the full load primary current.
Positive: 19 %
Answer #2 | 08/02 2014 10:06
0.3A.
Positive: 13 %