how many 12 gauge wires can 3/4 conduit hold ?

Answer this question

  • how many 12 gauge wires can 3/4 conduit hold ?


Answers

Answer #1 | 08/02 2014 11:41
Up to 16. Ampacity and wire fill tables are easy to find.
Positive: 33 %
Answer #2 | 08/02 2014 14:45
Lots of rules can apply, the most important being if using #12 conductors protected at 20 amps the max you can use is 9 current carrying conductors (plus a ground if needed). But if protecting at 15 amps, which is 50% of 310.15(B)(16) 90 degree column then: Depends on the conduit type, it ranges from 12 in schedule 80 PVC to 17 in IMC if using THHN. If the conduit is less than 24" then 18 to 25 are allowed (Chapter 9 table 1 note 4). And if stuffing romex through longer than 24" it requires 1" for one 12/2 or 3/4" for one 12/3 (53% fill, elliptical cables calculated as round conductor of major actual dimension).
Positive: 27 %

Possible answer

Ran across 3/4" with 14 #12 THHN in 3/4 " conduit.
Read more
Positive: 33 %
... five 10 gauge wires ... in 1/2" metal conduit. ... Maximum number of wires in 1/2" conduit; ... Can you even get 10, 12 gauge conductors to fit into a ...
Read more
Positive: 28 %
In a typical installation using 3/4 EMT and #12 AWG THHN wire, you would be able to fit 16 wires in the conduit per ... How many 12-gauge wires can you ...
Read more
Positive: 14 %
Conduit and Wire Review; ... Conduit Fill Table. Page Loading... Guides. ... 3/4 EMT: 22 16 10 6 4 ...